LAMINAR FLOW

UNI-FLOW INTEGRATED AIR & LIGHT CEILING

Bacteria cause infection within operating theatres.

In tests carried out by the UK Department of Health “Vertical Laminar Flow Ventilation” was found to reduce the amount of bacteria present in a typical operating theatre by a factor of up to 15,000”.

The Uni Flow Integrated Air and Lighting operating theatre ceilings are designed to meet the varying demandsof modem surgical techniques.

Modular Integration of the filtration,air diffusion, lightingand plenum champer solves the problems of coordinationencountered during construction.

Individually tailored to suit the customer’s requirements. Medikar offers a selection of ceilings to suitall surgical applications.

Supplied with optional Air-conditioning and control systems. Or as part of an existing mechanical services system, the Medikar range of specialist ceiling reduce the risk of post operative infection. Whils providing optimum comfort through the use of conditioned, filtered clean air.

The range of ventilated ceiling has been specifically designed for the application and is ideally suited for today’s surgical techniques.

Sim ultaneously solving the problems of coordination.Which may be encountered during the construction or relurbishment of the modern operating theatre departments.

The ceiling is available in a range of sizes, the standard being 2.40 Metres x 1.80 Metres completely integrated within the adjacent false ceiling.

The ceilings consist of a plenum box supplied with conditioned air from the central system via “S” class HEPA filters mounted on the inlet to the supply ceiling. The ceiling can include optional integral lighting, and composite air\light diffusers.

All HEPA filters and housings factory tested and certified.

All ceiling incorporate supports to secure them to the main structural frame of the modular operating theatre, or structural ceiling slab. The air\light diffusers consist of a monofilament precision woven polyester bonded to aluminium frames.

The screens have uniform porosity, with an open area of sufficient resistance to create laminar airflow from the diffuser face.

Diffusing air into the theatres, uniformly over the total are, the mgi range of ventilated ceiling provide the sterility and cleanliness required in today’s operating theatre environment. Optional integral lighting provides illumination across their total area.

Like this way it is also providing such problems which can hinder the integrity up from building of the stages of the modern operation theatre time till to using of this building.

With its illumination and diffuser variants designed system can meet all of the requirements from the OP Room Staff and it can also offer the customers variants of selections. Laminar Air Flooded OP Room Ceiling are produces in the standard sizes like 2,6 m x 2,4 m but it can also be produced variable to the customers requirement In bigger or smaller sizes in the condition that the functions will be the same. The produced Laminar Flow OP Room Cellings are In exact conform lty with the existent existent suspended ceiling.

System Design below paremeters must be controlled.
1- Tem perature
2- Humidity
3- Clean Air
4- Particie and Micro Organism number
5- Atmosphere Air Pressure
6- Air Condition (?)

Regarding the Opertion Type the Temperature of the OP Room can be wished low or high. The temperature of the OP Room must be as below;

DIN 1946/4,1989 22-26 C°.%30 - %65
DIN 1946/4.1999 22-26 C°.%30-%65
DIN 1946/4,2005 figure 19-26 C° can be arranged.

IMPORTANT FROM THE OP ROOM HUMIDITY

Humidity in the OP Room must be adjustable in accommodation conditions and if it is wished.

IMPORTANT FROM THE CLEAN AIR IN THE OP ROOM

It must be given to the OP Room filtered air to not increase the quality of the OP Room air.

Minimum clean air Debi must be as below;

DIN 1946/4,1989 1200 m³/
DIN 1946/4,1999 1200 m³/h
DIN 1946/4,2005 figure 1200 m³/h

Operation Room Feeding Air Debi DIN 1946/4,1989,1999
- Is depend to Temperture decrease or increase
- Mustn’t under the 2400 m³/h
-For the 1.A OP Room Theatres under the name Laminar Flow must be the air Debi 2400 m³/h and the pullution factor 0,67.

The OP Room Theatre air feeding rate 2005 figure must be for OP Rooms Operation table,instruments and opreation materials must be lower than linear flow.

This is approximately equivalent to 3x3 m², and it is changing to OP types.

Linear air flow capacity must be higher then 0,23 m /sec.

SPECIFICATION

The ceilings consist of a plenum box supplied with conditioned air from the central system via “S” class HEPA filters mounted on the inlet to the supply ceiling. The ceiling can inculude optional integral lighting,and composite air/light diffusers.

All HEPA filters and housings are factory tested and certified.

All ceilings incorporate supports to secure them to the main structural frame of the modular operating theatre,or structural ceiling slab.The air / light diffusers consist of a monofilament precision woven polyester bonded to aluminium frames.
The screens have uniform porosity,with an open area of sufficient resistance to create laminar airflow from the diffuser face.
Diffusing air into the theatres,uniformly over the total area,the mgi range of ventilated ceilings provide the sterility and cleanliness required in today’s operating theatre environment. Optional integral lighting provides illumination across their total area. Lighting is generated from high frequency electronic ballasts;complete with colour corrected flourescent tubes ensuring a confortable,shadowless working environment.

CHARACTERICTICS AND ADVANTAGES
  • Air conditioner which is passed through the “S” class HEPA filters.
  • Operator lamp which integrated to the system and eliminates the coordination and service problems.
  • Uniform backspace lighting.Between 1500-150 lux smooth adjustable lighting level.
  • Arbitrarily area lighting 
  • Produced complying with DIN 4799 and DIN 1946 and tested.In one meter cubic less then 10 bacterial carrier particle.
  • Expert MEDIKAR design,production,assembly and International service assurance.

fabrikamedikar

Medikar Hastane ve Tıbbi Sis. Yapı Taah. Tes. İmal. San. Tic. Ltd. Şti.

Address: Varlık Mahallesi,Beypazarı Caddesi No:21  ANKARA/Turkey

E-Mail: info@medikar.com Tel: +90 (312) 341 10 41 Fax: +90 (312) 341 10 42

Factory Address: Mersin Tarsus Organize Sanayi Bölgesi, Cumhuriyet Bulvarı No:13 MERSIN/Turkey

E-Mail: info@medikar.com

Tel: +90 (324) 645 40 41 - +90 (324) 645 40 42